Mailbox Messaging
User Manual
4.4.13 Mailbox Message: Class 2 Acyclic Data Write
This command issues a Class 2 DPV1 acyclic write request to a slave. Prior to
issuing this command, a connection to the slave must have been established,
see Initiate Class 2 Connection (page 110).
Parameter
Command Initiator
Command Name
Command Number
Fragmented
Command and Response Layout: Class 2 Acyclic Write
Message ID
Message information
Command
Data size
Frame count
Frame number
Offset high
Offset low
Extended word 1
Extended word 2
Extended word 3
Extended word 4
Extended word 5
Extended word 6
Extended word 7
Extended word 8
Message Data byte 1
Message Data byte 2
Message Data byte 3
Message Data byte (n)
Page 118 of 225
Description
Application
FB_APPL_MSAC2_WRITE
0028h
No
Command
(ID)
4002h
0028h
(data size)
0001h
0001h
0000h
0000h
C_REF
Slot
Index
Length
-
-
-
-
-
-
Write Data
---
MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform
Response
(ID)
0002h
0028h
Class 2 Acyclic Write
(data size)
Number of data bytes (n)
0001h
0001h
0000h
0000h
C_REF
Slot
Index
Length
-
-
Error
Decode
Error Code 1 Error Code 2
Extended Fault information
Fault Information
Write Data
Response Data byte 1
Response Data byte 2
Response Data byte 3
...
Response Data byte n
PROFIBUS DPV1 Master
ProSoft Technology, Inc.