Operating Guide | VACON® NXS/NXP Air-cooled
Procedure
1. If the AC drive must be stored before using it, make sure that the ambient conditions agree to the following:
•
Storage temperature: -40...+70° C (-40...+158° F)
•
Relative humidity: 0–95%, no condensation
2. If the AC drive must be kept in storage for a long time, connect the power to the AC drive each year. Keep the power on for a
minimum of 2 hours.
3. If the storage time is more than 12 months, charge the electrolytic DC capacitors with caution. To reform the capacitors, obey the
instructions in
10.2 Reforming the
We do not recommend a long storage time.
4.3 Lifting the Product
Context:
Lifting instructions depend on the weight of the AC drive. It can be necessary to use a lifting device to move the drive from its package.
Danfoss A/S © 2020.02
Capacitors.