Danfoss VACON NXS Series Operating Manual page 193

Air-cooled wall-mounted and standalone electronic motor controller
Hide thumbs Also See for VACON NXS Series:
Table of Contents

Advertisement

Operating Guide | VACON® NXS/NXP Air-cooled
Technical item or function
Functional safety
Hardware based 'Safe Torque
Off' safety function to prevent
the drive from generating tor-
que on the motor shaft.
STO safety function has been de-
signed for use in accordance
with the following standards
SS1 safety function is realized in
compliance with type C of the
drives safety standard
EN61800-5-2 (Type C: "The
PDS(SR) initiates the motor de-
celeration and initiates the STO
function after an application-
specific time delay").
SS1 safety function has been de-
signed for use in accordance
with the following standards:
ATEX thermistor input
Approvals
Efficiency
Control connections
Analog input voltage
(apply to boards OP-
TA1, OPTA2, and OP-
TA3)
Analog input current
Digital inputs (6)
Auxiliary voltage
Output reference voltage
Analog output
Digital outputs
Relay outputs
Danfoss A/S © 2020.02
Technical data
EN 61800-5-2 Safe Torque Off (STO) SIL3
EN ISO 13849-1 PL "e" Category 3
EN 62061 SILCL3
IEC 61508 SIL3
The function also corresponds to an uncontrolled stop in accord-
ance with stop category 0, EN 60204-1.
EN 954-1, Category 3
EN 61800-5-2 Safe Stop 1 (SS1) SIL3
EN ISO 13849-1 PL "e" Category 3
EN 62061 SILCL3
IEC 61508 SIL3
The function also corresponds to a controlled stop in accordance
with stop category 1, EN60204-1.
94/9/EC, CE 0537 Ex 11 (2) GD
CE, cULus, RCM, KC, EAC, UA. (See the nameplate of the drive for more
approvals.) Marine approvals: LR, BV, DNVGL, ABS, RMRS, CCS, KR, NK.
See
http://ecosmart.danfoss.com/
0...+10 V, Ri = 200 kΩ, (–10 V...+10 V joystick control)
®
Resolution 0.1% (VACON
NXP: 12-bit, VACON
±1%
0(4)-20 mA, Ri = 250 Ω differential
Positive or negative logic; 18–30 V DC
+24 V, ±10%, max volt. ripple < 100 mV rms; maximum 250 mA
Dimensioning: Maximum 1000 mA/control box (power back-up)
+10 V, +3%, maximum load 10 mA
0(4)–20 mA; RL maximum 500 Ω; Resolution 10 bit; Accuracy ±2%
Open collector output, 50 mA/48 V
2 programmable change-over relay outputs
Switching capacity (resistive): 24 VDC/8 A, 250 VAC/8 A, 125 VDC/0.4 A
Min.switching load: 5 V/10 mA
Specifications
®
NXS: 10-bit), accuracy
AQ275638903263en-000301 / DPD00910| 193

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vacon nxp series

Table of Contents