Operating Guide | VACON® NXS/NXP Air-cooled
Troubleshooting
Change the OPTAF board.
12.10.35 Fault 8 - System fault, Subcode S44 - OPTAF: STO channel 1 is not active, even if the analog
input supervision indicates
Cause
Single hardware problem detected in Safe Disable inputs or in the thermistor input.
Troubleshooting
Change the OPTAF board.
Change the control board.
12.10.36 Fault 8 - System fault, Subcode S45 - OPTAF: STO channel 2 is not active, even if the analog
input supervision indicates
Cause
Single hardware problem detected in Safe Disable inputs or in the thermistor input.
Troubleshooting
Change the OPTAF board.
Change the control board.
12.10.37 Fault 8 - System fault, Subcode S46 - OPTAF: Thermistor or analog input is not set, even if
STO is active
Cause
Single hardware problem detected in Safe Disable inputs or in the thermistor input.
Troubleshooting
Change the OPTAF board.
Change the control board.
12.10.38 Fault 8 - System fault, Subcode S47 - OPTAF: Board mounted in old NXP control board with
no safety hardware
Cause
OPTAF board mounted in old VACON
Troubleshooting
Change the control board to VB00561 revision H or newer.
Danfoss A/S © 2020.02
®
NXP control board, which is not equipped with the Safe Disable function.
Specifications
AQ275638903263en-000301 / DPD00910| 207