Cable And Fuse Sizes For 208-240 V And 380-500 V, Fr4 To Fr9, North America - Danfoss VACON NXS Series Operating Manual

Air-cooled wall-mounted and standalone electronic motor controller
Hide thumbs Also See for VACON NXS Series:
Table of Contents

Advertisement

Operating Guide | VACON® NXS/NXP Air-cooled
Enclosure
Drive type
size
FR8
0140 2
0140 5
0170 2
0168 5
0205 2
0205 5
FR9
0261 2
0261 5
0300 2
0300 5
1
Uses a correction factor 0.7
12.3.3 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9, North America
Table 41: Cable and Fuse Sizes for VACON
Enclo‐
Drive type
sure size
FR4
0003 2–0008 2
0003 5–0007 5
0009 5
0011 2–0012 2
0012 5
FR5
0017 2
0016 5
0025 2
0022 5
0031 2
0031 5
172 | Danfoss A/S © 2020.02
I
[A]
Fuse
Mains, motor and
L
(gG/gL) [A]
brake resistor cable Cu
(1)
140
160
3*70+35
168
200
3*95+50
205
250
3*150+70
261
315
3*185+95 or
2*(3*120+70)
300
315
2*(3*120+70)
®
NXS/NXP, North America
Fuse Class
Mains, Motor, and brake re‐
Fast Act‐
sistor cable Cu [AWG]
ing (T/J)
[A]
10
3*16 AWG + 16 AWG
15
3*16 AWG + 16 AWG
15
3*14 AWG + 14 AWG
20
3*12 AWG + 12 AWG
30
3*10 AWG + 10 AWG
40
3*8 AWG + 8 AWG
Mains terminal [mm
2
[mm
]
25–95 Cu/Al
95–185 Cu/Al
95–185 Cu/Al
95–185 Cu/Al
95–185 Cu/Al
Mains terminal [AWG]
(1) (2)
18 AWG - 4 AWG
18 AWG - 4 AWG
18 AWG - 4 AWG
18 AWG - 8 AWG
18 AWG - 8 AWG
18 AWG - 8 AWG
Specifications
Grounding terminal
2
]
2
[mm
]
6–95
6–95
6–95
6–95
6–95
Grounding terminal
[AWG]
18 AWG - 4 AWG
18 AWG - 4 AWG
18 AWG - 4 AWG
18 AWG - 8 AWG
18 AWG - 8 AWG
18 AWG - 8 AWG
AQ275638903263en-000301 / DPD00910