Danfoss VACON NXS Series Operating Manual page 190

Air-cooled wall-mounted and standalone electronic motor controller
Hide thumbs Also See for VACON NXS Series:
Table of Contents

Advertisement

Operating Guide | VACON® NXS/NXP Air-cooled
Technical item or function
Control qualities
Control method
Switching frequency (see param-
eter P2.6.9)
Frequency reference
Analog input
Panel reference
Field weakening point
Acceleration time
Deceleration time
Brake power
190 | Danfoss A/S © 2020.02
Technical data
Frequency control U/f, Open Loop Sensorless Vector Control, Closed
Loop Vector Control (VACON
208–240 V and 380–500 V, up to 0061: 1–16 kHz
Default: 6 kHz
208–240 V, 0075 and larger: 1–10 kHz
Default: 3.6 kHz
380–500 V, 0072 and larger: 1–6 kHz
Default: 3.6 kHz
525–690 V: 1–6 kHz
Default: 1.5 kHz
®
Resolution 0.1% (VACON
NXP: 12-bit), accuracy ±1%
Resolution 0.01 Hz
8–320 Hz
0.1–3000 s
0.1–3000 s
DC brake: 30% * TN (without the brake option)
Specifications
®
NXP only)
AQ275638903263en-000301 / DPD00910