Operating Guide | VACON® NXS/NXP Air-cooled
OPTA2
RO1/1
21
RO1/2
22
RO1/3
23
RO2/1
24
RO2/2
25
RO2/3
26
OPTA3
RO1/1
21
RO1/2
22
RO1/3
23
RO2/1
25
RO2/2
26
TI1+
28
TI1-
29
*) Parameter reference on control panel and NCDrive.
Illustration 51:
Control Terminal Signals on Relay Boards OPTA2 and OPTA3
X1
X2
Illustration 52:
OPTA2
108 | Danfoss A/S © 2020.02
Switching capacity
Relay output 1
• 24 VDC/8 A
• 250 VAC/8 A
DigOUT:B.1 *)
• 125 VDC/0.4 A
Minimum switching load
• 5 V/10 mA
Switching capacity
Relay output 2
• 24 VDC/8 A
• 250 VAC/8 A
DigOUT:B.2 *)
• 125 VDC/0.4 A
Minimum switching load
• 5 V/10 mA
Switching capacity
Relay output 1
• 24 VDC/8 A
• 250 VAC/8 A
• 125 VDC/0.4 A
Minimum switching load
DigOUT:B.1 *)
• 5 V/10 mA
Switching capacity
• 24 VDC/8 A
Relay output 2
• 250 VAC/8 A
• 125 VDC/0.4 A
Minimum switching load
DigOUT:B.2 *)
• 5 V/10 mA
Thermistor input
DigIN:B.1 *)
Control Unit
AQ275638903263en-000301 / DPD00910