Operating Guide | VACON® NXS/NXP Air-cooled
A
B
A The mains cable
C The motor cable
Illustration 28:
5. Put the cable entry plate with the cables into the groove on the frame of the drive. To attach the cable entry plate, use the M4x10
screws delivered in the accessories bag.
6. Connect the cables. See the correct tightening torques in
•
Connect the phase conductors of the mains cable and of the motor cable, and the conductors of the brake resistor cable into
the correct terminals.
•
Attach the grounding conductor of each cable with a grounding clamp.
7. Make sure to connect the grounding conductor to the motor and the terminals that are identified with the grounding symbol.
•
If a double grounding is necessary, use the grounding terminal below the drive. Use an M5 screw and tighten it to 2.0 Nm or
17.7 lb-in.
Danfoss A/S © 2020.02
C
Cables through the Cable Entry Plate
B The brake cable
12.6 Tightening Torques of the
Electrical Installation
Terminals.
AQ275638903263en-000301 / DPD00910| 73