Operating Guide | VACON® NXS/NXP Air-cooled
Table 61: Internal Brake Resistors, FR4–FR6
Enclosure size
Resistance [Ω]
FR4 (380–500 V)
120
FR5 (380–500 V)
55
FR6 (380–500 V)
30
1.20
1.00
0.80
0.60
0.40
0.20
0.00
0
2
4
6
8
A Time (s)
Illustration 82:
Relative Power Handling Capability of Internal Resistors

12.10 Faults and Alarms

12.10.1 Fault 1 - Overcurrent, Subcode S1- Hardware trip
Cause
There is too high a current in the motor cable. Its cause can be 1 of the following:
a sudden heavy load increase
a short circuit in the motor cables
the motor is not the correct type
Troubleshooting
Check the load.
Check the motor.
Check the cables and connections.
Make an identification run.
12.10.2 Fault 1 - Overcurrent, Subcode S2 - Current cutter supervision (VACON® NXS)
Cause
There is too high a current in the motor cable. Its cause can be 1 of the following:
a sudden heavy load increase
a short circuit in the motor cables
the motor is not the correct type
198 | Danfoss A/S © 2020.02
Energy 2 s full torque braking [kJ]
4
8.9
16
10
20
30
40
50
60
A
Specifications
Average power 1 pulse/min [W]
45
100
175
AQ275638903263en-000301 / DPD00910