4. Connect the cables. See the correct tightening torques in
Connect the phase conductors of the mains cable and of the motor cable into the correct terminals. If a brake resistor cable is
used, connect its conductors into the correct terminals.
Attach the grounding conductor of each cable to a grounding terminal with a grounding clamp for grounding conductor.
5. To make a 360° connection with the grounding clamp for cable shield, expose the shield of motor cables.
1
2
1 Grounding clamp
6. Attach the cable entry plate, and then the cable cover. For the tightening torques of the screws, see
Cover
Screws. Make sure that the control cables or the cables of the AC drive are not caught between the frame and the cable
cover.
Additional tightening torques:
motor cable entry plate: 2.4 Nm
control cable entry plate: 0.8 Nm
DC cover: 2.4 Nm
78 | Danfoss A/S © 2020.02
12.6 Tightening Torques of the
2 Exposed shield
Electrical Installation
Terminals.
12.5 Tightening Torques for
AQ275638903263en-000301 / DPD00910