Operating Guide | VACON® NXS/NXP Air-cooled
Procedure
1. To move the cables through grommets, cut them open.
Do not cut the grommet openings wider than what is necessary for the used cables.
If the grommets fold in when putting the cable, pull the cable back to make the grommets straight.
Cable gland can be used if preferred.
2. Attach the grommet and the cable until the frame of the drive goes into the groove of the grommet.
With the protection rating IP54 (UL Type 12), the connection between the grommet and the cable must be tight. Pull the first
bit of the cable out of the grommet until it stays straight.
If this is not possible, make the connection tight with some insulation tape or a cable tie.
3. To make a 360° connection with the grounding clamp for cable shield, expose the shield of motor cables.
4. Connect the cables. See the correct tightening torques in
A Connect the mains and motor cables. Use busbar to make the connection.
Danfoss A/S © 2020.02
12.6 Tightening Torques of the
Electrical Installation
Terminals.
AQ275638903263en-000301 / DPD00910| 85