12.10.21 Fault 8 - System fault, Subcode S30 - OPTAF: STO channels are different from each other
Cause
The Safe Disable inputs are in different states. It is not allowed according to EN954-1, category 3. This fault occurs when the Safe
Disable inputs are in different states for more than 5 s.
Troubleshooting
Check the S1 switch.
Check the cabling to the OPTAF board.
If the fault shows again, ask instructions from the local distributor.
12.10.22 Fault 8 - System fault, Subcode S31 - OPTAF: Thermistor short circuit detected
Cause
Thermistor short circuit detected.
Troubleshooting
Correct the cable connections.
Check the jumper for the thermistor short circuit supervision, if the thermistor function is not used and the thermistor input is
short-circuited.
12.10.23 Fault 8 - System fault, Subcode S32 - OPTAF board has been removed
Cause
OPTAF board has been removed. It is not allowed to remove the OPTAF board once the software has recognized it.
Troubleshooting
The system requires a manual acknowledgement using System menu parameter 6.5.5 OPTAF Remove. Ask help from the local
distributor.
12.10.24 Fault 8 - System fault, Subcode S33 - OPTAF: EEPROM error
Cause
OPTAF board EEPROM error (checksum, not answering and so on).
Troubleshooting
Change the OPTAF board.
12.10.25 Fault 8 - System fault, Subcode S34 - OPTAF: Voltage problem
Cause
OPTAF supply voltage hardware problem detected.