Operating Guide | VACON® NXS/NXP Air-cooled
Procedure
1. Strip the motor cable, the mains cable, and the brake resistor cable. See
2. Cut the grommets open to move the cables through them. Use the grommets delivered in the accessories bag.
Do not cut the grommet openings wider than what is necessary for the used cables.
If the grommets fold in when putting the cable, pull the cable back to make the grommets straight.
3. To achieve EMC class C1 and C2, use EMC cable gland as an alternative to the grommet.
1
3
4. Put the cables – the mains cable, the motor cable, and the optional brake cable – in the openings of the cable entry plate. Use the
cable entry plate delivered in the accessories bag.
68 | Danfoss A/S © 2020.02
2
4
12.4 Cable Stripping
Lengths.
AQ275638903263en-000301 / DPD00910
Electrical Installation