Operating Guide | VACON® NXS/NXP Air-cooled
Troubleshooting
Check the load.
Check the motor frame size.
Make an identification run.
Check brake resistor resistance.
12.10.99 Fault 42 - Brake resistor overtemperature, Subcode S1 - Internal brake chopper
overtemperature
Cause
Brake resistor overtemperature protection has detected too heavy braking.
Troubleshooting
Reset unit.
Set the deceleration time longer.
Dimensioning of the brake chopper is not correct.
Use external brake resistor.
12.10.100 Fault 42 - Brake resistor overtemperature, Subcode S2 - Brake resistance too high (BCU)
Cause
Brake resistor overtemperature protection has detected too heavy braking.
Troubleshooting
Reset unit.
Set the deceleration time longer.
Dimensioning of the brake chopper is not correct.
Use external brake resistor.
12.10.101 Fault 42 - Brake resistor overtemperature, Subcode S3 - Brake resistance too low (BCU)
Cause
Brake resistor overtemperature protection has detected too heavy braking.
Troubleshooting
Reset unit.
Set the deceleration time longer.
Dimensioning of the brake chopper is not correct.
Use external brake resistor.
Danfoss A/S © 2020.02