Installation
Airflow
The necessary airflow over the heat sink must be secured.
The flow rate is shown in Table 3.2.
NOTICE
The fan runs for the following reasons:
3
3
AMA
DC Hold
Pre-Mag
DC Brake
60% of nominal current is exceeded
Specific heatsink temperature exceeded (power
size dependent)
Specific Power Card ambient temperature
exceeded (power size dependent)
Specific Control Card ambient temperature
exceeded
Frame
Door fan/top fan
D1h/D3h
102 m
D2h/D4h
204 m
Table 3.2 Airflow

3.3.2 Lifting

Always lift the frequency converter using the dedicated
lifting eyes. Use a bar to avoid bending the lifting holes.
CAUTION
The angle from the top of the frequency converter to the
lifting cables should be 60° or greater.
10
Operating Instructions
Heatsink fan
3
3
/hr (60 CFM)
420 m
/hr (250 CFM)
3
3
/hr (120 CFM)
840 m
/hr (500 CFM)
Danfoss A/S © Rev. 2014-02-20 All rights reserved.
Illustration 3.1 Recommended Lifting Method
3.3.3 Wall Mounting - IP21 (NEMA 1) and
IP54 (NEMA 12) Units
Consider the following before selecting the final instal-
lation site:
Free space for cooling
Access to open the door
Cable entry from the bottom
MG34U302