Danfoss VACON NXS Series Operating Manual page 37

Air-cooled wall-mounted and standalone electronic motor controller
Hide thumbs Also See for VACON NXS Series:
Table of Contents

Advertisement

Operating Guide | VACON® NXS/NXP Air-cooled
Drive type
0075 2–0114 2
0072 5–0105 5
0041 6–0052 6
0140 2–0205 2
0140 5–0205 5
0062 6–0100 6
0261 2–0300 2
0261 5–0300 5
0125 6–0208 6
1
To change the fan with the motor cables connected, the necessary clearance on the 2 sides of the drive is 150 mm (5.91 inch).
2
The minimum clearance to change the fan.
Table 7: Required Cooling Air
Drive type
The quantity of cooling air [m
0003 2–0012 2
70
0003 5–0012 5
0017 2–0031 2
190
0016 5–0031 5
0048 2–0061 2
425
0038 5–0061 5
0004 6–0034 6
0075 2–0114 2
425
0072 5–0105 5
0041 6–0052 6
0140 2–0205 2
650
0140 5–0205 5
0062 6–0100 6
0261 2–0300 2
1000
0261 5–0300 5
0125 6–0208 6
Danfoss A/S © 2020.02
A
B
80
80
(3.15)
(3.15)
80
80
(3.15)
(3.15)
(1)
50
80
(1.97)
(3.15)
3
/h]
C
D
300
100
(11.81)
(3.94)
300
300
(11.81)
(11.81)
400
250 / 350
(15.75)
(9.84) / (13.78)
(2)
The quantity of cooling air [CFM]
41.2
112
250
250
383
589
AQ275638903263en-000301 / DPD00910| 37
Mounting the Unit