Operating Guide | VACON® NXS/NXP Air-cooled
12.3.4 Cable and Fuse Sizes for 525–690 V, FR6 to FR9
Table 42: Cable and Fuse Sizes for VACON
Enclosure
Drive type
size
FR6
0004 6–0007 6
0010 6–0013 6
0018 6
0022 6
0027 6–0034 6
FR7
0041 6
0052 6
FR8
0062 6–0080 6
0100 6
FR9
0125 6–0144 6
0170 6
0208 6
1
Uses a correction factor 0.7
174 | Danfoss A/S © 2020.02
®
NXS/NXP
I
[A]
Fuse
Mains, motor, and
L
(gG/gL) [A]
brake resistor ca‐
ble Cu
3–7
10
3*2.5+2.5
10–13
16
3*2.5+2.5
18
20
3*4+4
22
25
3*6+6
27–34
35
3*10+10
41
50
3*10+10
52
63
3*16+16
62–80
80
3*25+16
100
100
3*35+16
125–144
160
3*95+50
170
200
208
250
3*150+70
Mains terminal [mm
2
(1)
[mm
]
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
25–95 Cu/Al
95–185 Cu/Al
Specifications
Grounding terminal
2
]
2
[mm
]
2.5–35
2.5–35
2.5–35
2.5–35
2.5–35
6–50
6–50
6–95
6–95
AQ275638903263en-000301 / DPD00910