Danfoss VACON NXS Series Operating Manual page 186

Air-cooled wall-mounted and standalone electronic motor controller
Hide thumbs Also See for VACON NXS Series:
Table of Contents

Advertisement

Operating Guide | VACON® NXS/NXP Air-cooled
Enclosure
Drive
size
type
FR6
0038
0045
0061
FR7
0072
0087
0105
FR8
0140
0168
0205
FR9
0261
0300
0385
FR10
(3)
0460
0520
0590
FR11
(3)
0650
0730
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
12.7.1 Overload Capability
2
See
3
480 V
186 | Danfoss A/S © 2020.02
Input
Low
Low
current
loadabili‐
loadabili‐
ty: 10%
(1)
I
ty: I
[A]
in
L
overload
(2)
I [A]
38
38
42
46
46
49.5
61
61
67
72
72
79
87
87
96
105
105
116
140
140
154
170
170
187
205
205
226
261
261
287.1
300
300
330
385
385
424
460
460
506
520
520
576
590
590
649
650
650
715
730
730
803
High
High
Loadabil‐
loadabili‐
loadabili‐
ity: Max I
ty: 50%
ty: I
[A]
2 s
H
overload
(2)
I [A]
31
47
62
38
57
76
46
69
92
61
92
122
72
108
144
87
131
174
105
158
210
140
210
280
170
255
340
205
308
410
245
368
490
300
450
600
385
578
770
460
690
920
520
780
1040
590
885
1180
650
975
1300
Specifications
Motor
Motor
shaft
shaft
S
(3)
power
:
power
10% over‐
50% over‐
load
load
104°F [hp]
122°F [hp]
30
25
40
30
50
40
60
50
75
60
90
75
125
90
150
125
175
150
200
175
250
200
350
250
400
350
450
400
500
450
600
500
650
600
AQ275638903263en-000301 / DPD00910