Download Print this page

Specifications Of Input/Output Signals With Plc Cpu; List Of Input/Output Signals With Plc Cpu - Mitsubishi A1SD75P1-S3 User Manual

Advertisement

3 SPECIFICATIONS AND FUNCTIONS

3.4 Specifications of input/output signals with PLC CPU

3.4.1 List of input/output signals with PLC CPU

The AD75 uses 32 input points and 32 output points for exchanging data with the PLC
CPU.
The input/output signals for when the AD75 is mounted in slot No. 0 of the main base
unit are shown below.
Device X refers to the signals input from the AD75 to the PLC CPU, and device Y
refers to the signals output from the PLC CPU to the AD75.
Signal direction: AD75
Device No.
X0
X1
X2
X3
X4
X5
X6
X7
X8
X9
XA
XB
XC
XD
XE
XF
X10
X1F
Important
[Y15], [Y1E], [Y1F], [Y0 to YF] and [X10 to X1F] are used by the system, and cannot be used
by the user.
If used, the operation of the AD75 will not be guaranteed.
Note that when the AD75 is mounted on the remote I/O station, [YD] to [YF] can be turned
OFF in the user program.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
PLC CPU
Signal name
AD75 READY
Axis 1
Start complete
Axis 2
Axis 3
Axis 1
BUSY
Axis 2
Axis 3
Axis 1
Positioning complete
Axis 2
Axis 3
Axis 1
Error detection
Axis 2
Axis 3
Axis 1
M code ON
Axis 2
Axis 3
Use prohibited
3 - 12
Signal direction: PLC CPU
Device No.
Signal name
Y0
Use prohibited
YF
Y10
Axis 1
Y11
Axis 2
Positioning start
Y12
Axis 3
Y13
Axis 1
Axis stop
Y14
Axis 2
Y15
Use prohibited
Y16
Axis 1
Forward run JOG start
Y17
Axis 1
Reverse run JOG start
Y18
Axis 2
Forward run JOG start
Y19
Axis 2
Reverse run JOG start
Y1A
Axis 3
Forward run JOG start
Y1B
Axis 3
Reverse run JOG start
Y1C
Axis 3
Axis stop
Y1D
PLC READY
Y1E
Use prohibited
Y1F
MELSEC-A
AD75

Hide quick links:

Advertisement

loading

This manual is also suitable for:

A1sd75p2-s3A1sd75p3-s3Ad75p1-s3Ad75p2-s3Ad75p3-s3