List Of Input/Output Signals For The Programmable Controller Cpu - Mitsubishi QJ71C24N User Manual

Melsec-q series
Hide thumbs Also See for QJ71C24N:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.8 List of Input/Output Signals for the Programmable Controller CPU

Device
Signal description
number
CH1 Transmission normal completion
X0
1
ON: Normal completion
CH1 Transmission abnormal completion
X1
1
ON: Abnormal completion
CH1 Transmission processing
X2
1
ON: Transmission in progress
CH1 Reception data read request
X3
2
ON: Requesting read
CH1 Reception abnormal detection
X4
2
ON: Abnormal detection
X5
(For system)
CH1 Mode switching
X6
3
ON: Switching
CH2 Transmission normal completion
X7
1
ON: Normal Completion
CH2 Transmission abnormal completion
X8
1
ON: Abnormal completion
CH2 Transmission processing
X9
1
ON: Transmission in progress
CH2 Reception data read request
XA
2
ON: Requesting read
CH2 Reception abnormal detection
XB
2
ON: Abnormal detection
XC
(For system)
CH2 Mode switching
XD
3
ON: Switching
CH1 ERR. occurrence
XE
ON: Error occurring
CH2 ERR. occurrence
XF
ON: Error occurring
Modem initialization completion
X10
6
ON: Initialization completed
Dialing
X11
6
ON: Dial in progress
Connection
X12
6
ON: Connection in progress
Initialization/connection abnormal completion
X13
6
ON: Initialization/ connection abnormally completed
Modem disconnection complete
X14
6
ON: Disconnection completed
Notification normal completion
X15
6
ON: Normal completion
Notification abnormal completion
X16
6
ON: Abnormal completion
X17
1 Flash ROM read completion
X18
1 Flash ROM write completion
Flash ROM system setting write completion
X19
ON: Completed
3 - 20
This section describes the input/output signals of the Q series C24.
The following I/O signal assignment is based on the case where the start I/O No. of the
Q series C24 is "0000" (installed to slot 0 of the main base unit).
Device numbers starting with X indicate input signals from the Q series C24 to the
programmable controller CPU.
Device numbers starting with Y indicate output signals from the programmable
controller CPU to the Q series C24.
The following table lists the input/output signals for the programmable controller CPU.
Reference
Section 9.6.4
Section 9.6.5
Section 9.6.6
Section 6.1
Section 7.1
Section 9.6.5
Section 9.6.6
Application
Section 9.6.4
Section 9.6.5
Section 9.6.6
Section 6.1
Section 7.1
Section 9.6.5
Section 9.6.6
Application
Section 9.6.11
Section 11.1.2
Section 9.6.2
Application
ON: Completed
ON: Completed
Device
section
number
CH1 Transmission request
Y0
ON: Requesting transmission
CH1 Reception data read completion
Y1
ON: Data read completed
CH1 Mode switching request
Y2
ON: Requesting switch
Y3
Y4
Y5
Y6
CH2 Transmission request
Y7
ON: Requesting transmission
CH2 Reception data read completion
Y8
ON: Data read completed
CH2 Mode switching request
Y9
ON: Requesting switch
YA
YB
YC
YD
CH1 ERR.clear request
YE
ON: Requesting error clear
CH2 ERR. clear request
YF
ON: Requesting error clear
Modem initialization request (standby request)
Y10
6
ON: Requesting initialization
Connection request
Y11
6
ON: Requesting connection
Modem disconnection request
Y12
6
ON: Requesting disconnection
Y13
Notification- issued request
Y14
6
OFF: Requesting notification issuance
Y15
Y16
Y17
Flash ROM read request
Y18
Flash ROM write request
Flash ROM system setting write request
Y19
ON: Requesting
MELSEC-Q
Signal description
Use prohibited
Use prohibited
Use prohibited
Use prohibited
ON: Requesting
ON: Requesting
Reference
section
Application
Application
Section 9.6.11
Section 11.1.2
Section 9.6.2
Application
3 - 20

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qj71c24n-r2Qj71c24n-r4Qj71c24Qj71c24-r2

Table of Contents