Mitsubishi A1SD75P1-S3 User Manual page 518

Advertisement

14 TROUBLESHOOTING
Relevant buffer memory address
Axis 1
Axis 2
Axis 3
Refer to sections 5.2.1 to 5.2.6
and 5.3.
Refer to sections 5.2.1 to 5.2.6
and 5.3.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting range
(Setting given in sequence program)
<Position data, positioning address/movement
amount in parameter>
(In stepping motor mode)
• [mm] [inch] [pulse]
-134217728 to 134217727
• [degree]
INC: -134217728 to 134217727
ABC: 0 to 35999999
• Speed/position changeover
0 to 134217727
<Speed data of parameter and command speed
of positioning data>
1 to 62500 [pulse/s]
1 to 37500000 [mm/min, etc.]
14 - 7
MELSEC-A
Remedy
• Check if there are effects of noise or the like.
• Check for hardware errors.
• Correct the position data in the parameter to
within the setting range of the stepping motor
mode specified in sections 5.2.1 to 5.2.6.
• Change the positioning address/movement
amount to within the setting range for the
stepping motor specified in section 5.3.
• Correct the speed data of the parameter to
within the setting range for the stepping motor
mode specified in sections 5.2.1 to 5.2.6.
• Correct the command speed of the positioning
data to within the setting range for the
stepping motor mode specified in section 5.3.
Remove the cause of stopping and perform axis
error resetting (refer to [3] in section 14.1) to
remove the error.
• Examine the sequence program in which the
"PLC READY" signal (Y1D) is turned ON or
OFF.
• Perform axis error resetting (refer to [3] in
section 14.1) to remove the error.
Check the state of the power supply of the drive
unit and the wiring to the drive unit and the
connection state of the connectors, and perform
axis error resetting (refer to [3] in section 14.1)
to remove the error.