Advertisement

5.
Set "Basic Setting" of "Module Parameter" of the temperature control module as shown below.
[Navigation window]  [Parameter]  [Module Information]  [R60TCTRT2TT2]  [Basic Setting]
6.
Set "Application Setting" of "Module Parameter" of the temperature control module as shown below.
[Navigation window]  [Parameter]  [Module Information]  [R60TCTRT2TT2]  [Application Setting]
• "Control basic parameters"
Set "Target Value (SV) Setting" of CH1 and "Unused channel setting" of CH2 to CH4 as shown below.
7.
Set "Refresh" of "Module Parameter" of the temperature control module as shown below.
[Navigation window]  [Parameter]  [Module Information]  [R60TCTRT2TT2]  [Refresh]
8.
Write the set parameters to the remote head module on the intelligent device station. Then reset the remote head
module or power OFF and ON the system.
[Online]  [Write to PLC]
For parameters of the master/local module which are not described in this procedure, set default values. For
details on parameters of the master/local module, refer to the following:
MELSEC iQ-R CC-Link IE Field Network Remote Head Module User's Manual (Application)
Appendix 5 Operation Examples of When the Remote Head Module Is Mounted