Mitsubishi Electric MELSEC iQ-R Series User Manual page 317

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Sensor two-point correction gain value (corrected value)
The correction value of the temperature corresponding to the sensor two-point correction gain value is stored in this buffer
memory area. For details on the sensor two-point correction function, refer to the following:
Page 59 Sensor Correction Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Sensor two-point correction gain value (corrected value)
CH Sensor two-point correction gain value (corrected value) (in the Q
compatible mode)
■Setting range
The temperature measuring range set in 'CH1 Input range' (Un\G501) ( Page 254 CH1 Input range)
■Setting unit
The value to be set differs depending on the value stored in 'CH1 Decimal point position' (Un\G400). ( Page 229 CH1
Decimal point position)
• No decimal point (0): Set a value in increments of 1 ( or digit).
• First decimal place (1): Set a value (the value multiplied by 10) in increments of 0.1 ().
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is 0.
CH1 Number of moving averaging setting
Set the number of moving averaging to be executed to temperature process values (PV).
For details on the moving average processing to temperature process values (PV), refer to the following:
Page 68 Moving Average Processing
This setting is enabled only when 'Moving average processing setting' (Un\G305) has been set to Enable (0).
This setting is disabled when 'Moving average processing setting' (Un\G305) has been set to Disable (1).
For details on 'Moving average processing setting' (Un\G305), refer to the following:
Page 226 Moving average processing setting
In the Q compatible mode, set the number of moving averaging in 'Moving average processing setting' (in the
Q compatible mode) (Un\G1024, b3).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Number of moving averaging setting
CH Number of moving averaging setting (in the Q compatible mode)
■Setting range
2 to 10 (times)
■Default value
The default value is 2 (times).
CH1
CH2
571
771
547
579
CH1
CH2
572
772
698
699
Appendix 3 Buffer Memory Areas
CH3
CH4
971
1171
611
643
CH3
CH4
972
1172
700
701
APPX
315
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60tctrt2tt2R60tcrt4R60tctrt2tt2bwR60tcrt4bw