CH1 Cooling control output cycle setting
Set the pulse cycle (ON/OFF cycle) of the transistor output.
The ON time of the control output cycle is determined by multiplying the control output cycle by the manipulated value for
cooling (MVc) (%) calculated by a PID operation. When the manipulated value for cooling (MVc) is stable, pulses are
repeatedly output in the same cycle. For details on this area, refer to the following:
Page 261 CH1 Control output cycle setting
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Cooling control output cycle setting
CH Cooling control output cycle setting (in the Q compatible mode)
CH1 Cooling method setting
Set a cooling control method in the heating-cooling control. Select a cooling method suitable for cooling characteristics of
devices.
For details on the cooling method setting function, refer to the following:
Page 34 Cooling Method Setting Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Cooling method setting
■Setting range
• 0H: Air cooling
• 1H: Water cooling
• 2H: Linear
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is Air cooling (0H).
APPX
278
Appendix 3 Buffer Memory Areas
CH1
CH2
522
722
722
738
CH1
CH2
523
723
CH3
CH4
922
1122
754
770
CH3
CH4
923
1123

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60tctrt2tt2R60tcrt4R60tctrt2tt2bwR60tcrt4bw

Table of Contents