■When executing the auto tuning
Set AUTO (0). When MAN (1) has been set, the auto tuning is not executed.
■Default value
The default value is AUTO (0).
CH1 MAN output setting
This buffer memory area is used to set the manipulated value (MV) in the MAN mode.
Even though writing of data is executed during control in the AUTO mode, the setting values do not change.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH MAN output setting
CH MAN output setting (in the Q compatible mode)
■How to shift the mode
Change the mode with the following buffer memory area:
• 'CH1 AUTO/MAN mode shift' (Un\G518) ( Page 274 CH1 AUTO/MAN mode shift)
■Setting range
The setting range differs depending on the standard control and the heating-cooling control. ( Page 15 Control Mode
Selection Function)
• Standard control: -50 to 1050 (-5.0 to 105.0%)
• Heating-cooling control: -1050 to 1050 (-105.0 to 105.0%)
■Enabling the settings
Before writing a value in MAN output setting, check that the target bit of 'MAN mode shift completion flag' (Un\G44) is ON.
A value that has been written while MAN mode shift completion flag is OFF will be replaced with the manipulated value (MV)
that the system calculated with the PID operation.
■Default value
The default value is 0 (0.0%).
CH1
CH2
519
719
51
83
Appendix 3 Buffer Memory Areas
CH3
CH4
919
1119
115
147
APPX
275