Mitsubishi Electric MELSEC iQ-R Series User Manual page 228

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Control output cycle unit selection setting
Select 0.1s or 1s as the unit of the transistor output ON/OFF cycle.
• 0: 1s cycle
• 1: 0.1s cycle
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
Control output cycle unit selection setting
■Default value
The default value is 1s cycle (0).
When the control output cycle unit has been changed, the control output cycle setting, heating control output
cycle setting, and cooling control output cycle setting are overwritten with their default values. A set value
discrepancy error (control output cycle unit selection setting) (error code: 1920H) occurs right after the control
output cycle unit selection setting change. To clear the error, turn from OFF to ON 'Setting value backup
command' (Y8) and register the parameter after the change in the non-volatile memory.
Moving average processing setting
Set whether to enable or disable the moving average processing.
• 0: Enable
• 1: Disable
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
Moving average processing setting
■Default value
The default value is 0.
PID continuation flag
Set the operation status at the time when the mode has shifted from the operation mode to the setting mode (when 'Setting/
operation mode command' (Y1) is turned from ON to OFF).
For details on the relation between the setting of this flag and the control status, refer to the following:
• PID control ( Page 23 Condition to execute the PID control)
• Temperature judgment ( Page 230 CH1 Alert definition)
• Alert judgment ( Page 79 Condition for alert judgment)
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
PID continuation flag
PID continuation flag (in the Q compatible mode)
■Setting range
• 0: Stop
• 1: Continue
■Default value
The default value is Stop (0).
APPX
226
Appendix 3 Buffer Memory Areas
CH1
CH2
304
CH1
CH2
305
CH1
CH2
306
169
CH3
CH4
CH3
CH4
CH3
CH4

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60tctrt2tt2R60tcrt4R60tctrt2tt2bwR60tcrt4bw