CH1 Temperature rise completion soak time setting
Set the time taken to set 'CH1 Temperature rise judgment flag' (Un\G404) to Within temperature rise completion range (1)
after the completion of the temperature rise.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Temperature rise completion soak time setting
Temperature rise completion soak time setting (in the Q compatible mode)
■Setting range
The setting range is 0 to 3600 (min).
■Default value
The default value is 0 (min).
CH1 Upper limit output limiter
Set the upper limit value for actually outputting the manipulated value (MV) calculated by the PID operation to an external
device.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Upper limit output limiter
CH Upper limit output limiter (in the Q compatible mode)
■Setting range
The setting range is -50 to 1050 (-5.0 to 105.0%).
Set values so that the lower limit output limiter value is smaller than the upper limit output limiter value.
When the lower limit output limiter value is equal to or greater than the upper limit output limiter value, CH Upper/lower limit
output limiter setting error (error code: 1A0H) occurs.
When a value out of the setting value is set, an out of setting range error (error code: 1950H) occurs. When an error has
occurred, the following operations will be executed:
• 'Error flag' (X2) turns ON.
• An error code is stored in 'Latest error code' (Un\G0).
'CH1 Cooling upper limit output limiter' (Un\G521) is disabled even a value has been set.
■Two-position control
In the two-position control, this setting is disabled.
■Manual control
In the manual control, this setting is enabled.
When an output to an external device exceeds the upper limit output limiter value, the manipulated value (MV) of the manual
control is fixed (clipped) to the set upper limit output limiter value.
■Default value
The default value is 1000 (100.0%).
CH1
CH2
507
707
168
CH1
CH2
508
708
42
74
Appendix 3 Buffer Memory Areas
CH3
CH4
907
1107
CH3
CH4
908
1108
106
138
APPX
265
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60tctrt2tt2R60tcrt4R60tctrt2tt2bwR60tcrt4bw

Table of Contents