■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Integration output limiter setting
CH Integration output limiter setting (in the Q compatible mode)
■Setting range
Set a value within the range of 0 to 2000 (0.0 to 200.0%) for the setting value of 'CH1 Control motor time' (Un\G528). (0.0:
Integration output limiter function OFF)
■Default value
The default value is 1500 (150.0%).
CH1 Valve operation setting during CPU module STOP
Set the operation of the open side output and close side output of when the control stops (STOP).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Valve operation setting during CPU module STOP
CH Valve operation setting during CPU module STOP (in the Q compatible
mode)
■Setting range
• 0: Close side output OFF, open side output OFF
• 1: Close side output ON, open side output OFF
• 2: Close side output OFF, open side output ON
■Default value
The default value is Close side output OFF, open side output OFF (0).
CH1
CH2
529
729
1042
1058
CH1
CH2
530
730
1043
1059
Appendix 3 Buffer Memory Areas
CH3
CH4
929
1129
1074
1090
CH3
CH4
930
1130
1075
1091
APPX
283
A