■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Integration output limiter setting
CH Integration output limiter setting (in the Q compatible mode)
■Setting range
Set a value within the range of 0 to 2000 (0.0 to 200.0%) for the setting value of 'CH1 Control motor time' (Un\G528). (0.0:
Integration output limiter function OFF)
■Default value
The default value is 1500 (150.0%).
CH1 Valve operation setting during CPU module STOP
Set the operation of the open side output and close side output of when the control stops (STOP).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Valve operation setting during CPU module STOP
CH Valve operation setting during CPU module STOP (in the Q compatible
mode)
■Setting range
• 0: Close side output OFF, open side output OFF
• 1: Close side output ON, open side output OFF
• 2: Close side output OFF, open side output ON
■Default value
The default value is Close side output OFF, open side output OFF (0).
CH1
CH2
529
729
1042
1058
CH1
CH2
530
730
1043
1059
Appendix 3 Buffer Memory Areas
CH3
CH4
929
1129
1074
1090
CH3
CH4
930
1130
1075
1091
APPX
283
A