Position proportional control
The following shows the relation among the setting, error, and the operation of the CPU module.
Status
HOLD/CLEAR setting
PID continuation flag
CPU module status
RUN
Stop error
Operation of the
RUNSTOP
CPU module
Resetting
*1
Disconnection
*1 When the module is mounted together with a remote head module
Precautions
• Fully pay attention to the settings of "PID continuation Flag" of "Control basic parameters" in "Application Setting" and
"Valve operation setting (When CPU stop)" of "Position-proportional control setting" in "Application Setting" for controlling
external outputs.
• Depending on an output element failure or an internal circuit failure, an abnormal output may occur. Configure an external
circuit for monitoring output signals that could cause a serious accident.
Setting method
Configure the setting as follows:
[Navigation window]  [Parameter]  Target module  [Base Setting]  [HOLD/CLEAR setting]
1 FUNCTIONS
28
1.5 HOLD/CLEAR Function
Processing
CLEAR
Stop
Continue
The temperature judgment and warning judgment are executed and the external output is executed.
The temperature judgment and warning judgment stop
and the external output is turned OFF.
The temperature judgment
The temperature
and warning judgment
judgment and warning
depend on the stop mode
judgment are executed
setting of "Control basic
and the external output
parameters" in "Application
is executed.
Setting," and the external
output depends on "Valve
operation setting (When CPU
stop)."
The module is inoperative, and does not execute external outputs.
The temperature judgment
The temperature
and warning judgment
judgment and warning
depend on the stop mode
judgment are executed
setting of "Control basic
and the external output
parameters" in "Application
is executed.
Setting," and the external
output depends on "Valve
operation setting (When CPU
stop)."
HOLD
Stop
Continue
The temperature judgment
The temperature
and warning judgment
judgment and warning
depend on the stop mode
judgment are executed
setting of "Control basic
and the external output
parameters" in "Application
is executed.
Setting," and the external
output depends on "Valve
operation setting (When CPU
stop)."
The temperature judgment
The temperature
and warning judgment
judgment and warning
depend on the stop mode
judgment are executed
setting of "Control basic
and the external output
parameters" in "Application
is executed.
Setting," and the external
output depends on "Valve
operation setting (When CPU
stop)."
The temperature judgment
The temperature
and warning judgment
judgment and warning
depend on the stop mode
judgment are executed
setting of "Control basic
and the external output
parameters" in "Application
is executed.
Setting," and the external
output depends on "Valve
operation setting (When CPU
stop)."