3.5
List of Alarm Codes
If an alarm occurs in operation of the temperature control module, the alarm code of the alarm is stored into 'Latest alarm
code' (Un\G3) of the buffer memory. Turning ON and OFF 'Error reset command' (Y2) clears the alarm code in 'Latest alarm
code' (Un\G3).
in alarm codes: This symbol indicates the number of the channel where an alarm has occurred. (1: CH1, 2: CH2, 3: CH3, 4:
CH4)
Alarm code
Alarm name
080H
CH Process value (PV) out of
input range (upper limit)
081H
CH Process value (PV) out of
input range (lower limit)
082H
CH Rate alarm (upper limit)
083H
CH Rate alarm (lower limit)
084H
CH Alert 1
085H
CH Alert 2
086H
CH Alert 3
087H
CH Alert 4
088H
CH Heater disconnection
detection
089H
CH Loop disconnection
detection
08AH
CH Output off-time current error
detection
Description and cause
The temperature process value (PV)
has exceeded the temperature
measuring range that was set as the
input range.
The temperature process value (PV)
is below the temperature measuring
range that was set as the input range.
A rate alarm (upper limit) has
occurred.
A rate alarm (lower limit) has
occurred.
Alert 1 has occurred.
Alert 2 has occurred.
Alert 3 has occurred.
Alert 4 has occurred.
A heater disconnection has been
detected.
A loop disconnection has been
detected.
An output off-time current error has
been detected.
Action
After the temperature process value (PV) falls within the
setting range, turn ON and OFF 'Error reset command'
(Y2) to clear the alarm code stored in 'Latest alarm code'
(Un\G3).
After the temperature process value (PV) falls within the
setting range, the corresponding bit of Alert definition and
'CH Alert flag' (XC to XF) automatically turn OFF.
After the temperature process value (PV) is restored from
the alert status, turn ON and OFF 'Error reset command'
(Y2) to clear the alarm code stored in 'Latest alarm code'
(Un\G3).
After the temperature process value (PV) is restored from
the alert status, the corresponding bit of Alert definition
and 'CH Alert flag' (XC to XF) automatically turn OFF.
After the temperature process value (PV) is restored from
the alert status, turn ON and OFF 'Error reset command'
(Y2) to clear the alarm code stored in 'Latest alarm code'
(Un\G3).
After the temperature process value (PV) is restored from
the alert status, the corresponding bit of Alert definition
and 'CH Alert flag' (XC to XF) automatically turn OFF.
After the detected disconnection or the detected output
off-time current error is resolved, turn ON and OFF 'Error
reset command' (Y2) to clear the alarm code stored in
'Latest alarm code' (Un\G3).
After the detected disconnection or the detected output
off-time current error is resolved, the corresponding bit of
Alert definition and 'CH Alert flag' (XC to XF)
automatically turn OFF.