CH1 Heating proportional band (Ph) setting
Set the heating proportional band (Ph) to execute the PID control. For details on this area, refer to the following:
Page 245 CH1 Proportional band (P) setting
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Heating proportional band (Ph) setting
CH Heating proportional band (Ph) setting (in the Q compatible mode)
■Setting range
• In the R mode
0 to the full scale of the input range (())
• In the Q compatible mode
0 to 10000 (0.0% to 1000.0%)
■Two-position control
Set the heating proportional band (Ph) to 0.
For details on the two-position control, refer to the following:
Page 18 Control Method
■Default value
• In the R mode
For the R60TCTRT2TT2 and the R60TCTRT2TT2BW, the default value is 30 (30).
For the R60TCRT4 and the R60TCRT4BW, the default value is 30 (3.0).
• In the Q compatible mode
The default value is 30 (3.0%).
CH1 Integral time (I) setting
Set the integral time (I) to execute the PID control.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Integral time (I) setting
CH Integral time (I) setting (in the Q compatible mode)
■Setting range
• Other than the position-proportional control
The setting range is 0 to 3600 (0 to 3600s).
• Position-proportional control
The setting range is 1 to 3600 (1 to 3600s).
■P control or PD control
Set 0. For details on control methods, refer to the following:
Page 18 Control Method
■Default value
The default value is 240 (240s).
CH1
CH2
431
631
35
67
CH1
CH2
432
632
36
68
Appendix 3 Buffer Memory Areas