Mitsubishi Electric MELSEC iQ-R Series User Manual page 303

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Peak current suppression control group setting [Q compatible mode]
In the Q compatible mode, set the target channel of the peak current suppression function and the width of the control output
cycle to be shifted for each channel.
For details on the peak current suppression function, refer to the following:
Page 95 Peak Current Suppression Function
When the inter-module peak current suppression function has been enabled, up to 5 groups can be set.
to
to
b15
b12 b11
CH4
CH3
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
Peak current suppression control group setting [in the Q compatible mode]
■Setting range
• 0: Not divided
• 1: 1 group
• 2: 2 groups
• 3: 3 groups
• 4: 4 groups
• 5: 5 groups (when the inter-module peak current suppression function is enabled)
■Number of divisions
The number of divisions is determined by this setting. The upper limit output limiter value is automatically set depending on
the set number of divisions. At the timing of when this setting is enabled, the following values are set:
Number of divisions
2
3
4
5
'CH1 Lower limit output limiter' (in the Q compatible mode) (Un\G43) is set to 0.
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is Not divided (0H).
to
to
b8
b7
b4
b3
CH2
CH1
'CH1 Upper limit output limiter' (in the Q compatible mode) (Un\G42)
500 (50.0%)
333 (33.3%)
250 (25.0%)
200 (20.0%)
b0
CH1
CH2
784
Appendix 3 Buffer Memory Areas
CH3
CH4
APPX
301
A