CH1 Rate alarm alert output enable/disable setting
Set whether to enable or disable alert output of rate alarms. For details on rate alarms, refer to the following:
Page 82 Rate Alarm Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Rate alarm alert output enable/disable setting
CH Rate alarm alert output enable/disable setting (in the Q compatible mode)
■Setting range
• 0: Enable
• 1: Disable
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is Disable (1).
CH1 Rate alarm alert detection cycle
Set the checking cycle of the temperature process value (PV) at the occurrence of a rate alarm. Set the frequency of checks
in increments of sampling cycles. The checking cycle can be calculated by the following formula:
• Rate alarm alert detection cycle = Set value of Rate alarm alert detection cycle Sampling cycle
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Rate alarm alert detection cycle
CH Rate alarm alert detection cycle (in the Q compatible mode)
■Setting range
The setting range is 1 to 6000 (times).
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is 1 (check the value every sampling cycle).