P control
P control is a control method in which the manipulated value (MV) is determined proportional to the deviation (E) between the
temperature process value (PV) and set value (SV).
■Standard control
The manipulated value (MV) is 50% in the following conditions:
• Temperature process value (PV) = Set value (SV)
• 'CH1 Manual reset amount setting' (Un\G517) has been set to 0 (0.0%) (Page 274 CH1 Manual reset amount setting).
*1
Manipulated value (MV)
100%
50%
0%
*1 A value to be actually output is within the output limiter range set in "Upper limit output limiter" and "Lower limit output limiter" of "Limiter
setting" in "Application Setting."
*2 The set value (SV) is the center of the proportional band (P).
■Heating-cooling control
The manipulated value for heating (MVh) and the manipulated value for cooling (MVc) are both 0% in the following conditions:
• Temperature process value (PV) = Set value (SV)
• 'CH1 Manual reset amount setting' (Un\G517) has been set to 0 (0.0%) (Page 274 CH1 Manual reset amount setting).
Manipulated value
for heating (MVh)
100%
0%
Heating proportional
*1 A value to be actually output is within the output limiter range set in "Upper limit output limiter" and "Lower limit output limiter" of "Limiter
setting" in "Application Setting." (Page 136 Application Setting)
1 FUNCTIONS
20
1.2 Control Method
*2
Set value (SV)
Proportional band (P)
Manipulated value
*1
for cooling (MVc)
Set value (SV)
Cooling proportional
band (Pc)
band (Ph)
Temperature process
value (PV)
*1
Temperature process
value (PV)