Advertisement

CH1 Peak current suppression control group setting
Set the target channel of the peak current suppression function and the width of the control output cycle to be shifted for each
channel.
For details on the peak current suppression function, refer to the following:
Page 95 Peak Current Suppression Function
When the inter-module peak current suppression function has been enabled, up to 5 groups can be set.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Peak current suppression control group setting
■Setting range
• 0: Not divided
• 1: 1 group
• 2: 2 groups
• 3: 3 groups
• 4: 4 groups
• 5: 5 groups (when the inter-module peak current suppression function is enabled)
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Default value
The default value is Not divided (0H).
APPX
300
Appendix 3 Buffer Memory Areas