Mitsubishi Electric MELSEC iQ-R Series User Manual page 184

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Address:
CH
Setting details
Decimal
Standard
(hexadeci
control
mal)
1006(3EEH)
CH4
Set value (SV)
monitor
1007(3EFH)
CH4
Manipulated
value (MV) for
output with
another analog
module
1008(3F0H)
CH4
System area
1009(3F1H)
CH4
System area
1010(3F2H)
CH4
System area
1011(3F3H)
CH4
Self-tuning flag
1012(3F4H)
CH4
Process value
(PV) scaling
value
1013(3F5H)
CH4
AT simultaneous
temperature rise
parameter
calculation flag
1014(3F6H)
CH4
Simultaneous
temperature rise
status
1015(3F7H)
CH4
Feed forward
control forced
start status
1016(3F8H)
CH4
Feed forward
value tuning flag
1017(3F9H)
CH4
Feed forward control READY flag
1018(3FAH)
CH4
Feed forward control forced start READY flag
1019(3FBH)
CH4
Sensor two-point correction offset latch completion
1020(3FCH)
CH4
Sensor two-point correction gain latch completion
1021 to 1029
System area
(3FDH to
405H)
1030(406H)
CH4
Set value (SV)
setting
1031(407H)
CH4
Proportional
band (P) setting
1032(408H)
CH4
Integral time (I)
setting
1033(409H)
CH4
Derivative time
(D) setting
1034(40AH)
CH4
Alert set value 1
1035(40BH)
CH4
Alert set value 2
1036(40CH)
CH4
Alert set value 3
APPX
182
Appendix 3 Buffer Memory Areas
Heating-
Mix control
cooling
control
Set value (SV)
Set value (SV)
*4
monitor
monitor
Manipulated
Manipulated
value for heating
value (MV) for
(MVh) for output
output with
with another
another analog
*4
analog module
module
Manipulated
System area
value for cooling
*4
(MVc)
Manipulated
System area
value for cooling
(MVc) for output
with another
*4
analog module
Cooling
System area
transistor output
*4
flag
System area
Self-tuning flag
Process value
Process value
(PV) scaling
(PV) scaling
*4
value
value
System area
AT simultaneous
temperature rise
parameter
calculation flag
System area
Simultaneous
temperature rise
status
Feed forward
Feed forward
control forced
control forced
*4
start status
start status
Feed forward
Feed forward
value tuning
value tuning flag
*4
flag
Set value (SV)
Set value (SV)
*4
setting
setting
Heating
Proportional
proportional
band (P) setting
band (Ph)
*4
setting
Integral time (I)
Integral time (I)
*4
setting
setting
Derivative time
Derivative time
*4
(D) setting
(D) setting
Alert set value
Alert set value 1
*4
1
Alert set value
Alert set value 2
*4
2
Alert set value
Alert set value 3
*4
3
Default
value
Position-
proportional
control
Set value (SV)
0
*8
monitor
System area
0
System area
0
System area
0
Close side
0
transistor output
*8
flag
System area
0
Process value
0
(PV) scaling
*8
value
System area
0
System area
0
System area
0
System area
0
System area
0
System area
0
0
0
Set value (SV)
0
*8
setting
Proportional
30
band (P)
*8
setting
Integral time (I)
240
*8
setting
Derivative time
60
*8
(D) setting
Alert set value
0
*8
1
Alert set value
0
*8
2
Alert set value
0
*8
3
Data
(1)
(2)
(3)
(4)
type
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Control
Control
Control
Control
Control
Control
Control
(5)

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60tctrt2tt2R60tcrt4R60tctrt2tt2bwR60tcrt4bw

Table of Contents