■Setting range
Setting
Setting
Description
value
details
0
Slow
Set this value when reducing the overshoot and undershoot to the change of the set value (SV). However, the settling time
becomes the longest among the three settings.
1
Normal
This setting has features between Slow and Fast.
2
Fast
Set this value when hastening the response to the change of the set value (SV). However, the overshoot and undershoot
become the largest among the three settings.
Temperature process value (PV)
Set value (SV) 2
Change
Set value (SV) 1
Using the overshoot suppression function and setting the control response parameter to Fast (2) raise
temperatures at a high speed while suppressing the overshoot. For the overshoot suppression function, refer
to the following:
Page 125 Overshoot Suppression Function
■Default value
The default value is Slow (0).
Fast
Set value (SV) change point
Normal
Slow
Time
Appendix 3 Buffer Memory Areas
A
APPX
263