CH1 Setting variation rate limiter (temperature drop)
This area is used when the individual setting has been selected with 'Automatic setting at input range change' (Un\G302) or
'Sampling cycle and function extension setting' (in the Q compatible mode) (Un\G1024).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Setting variation rate limiter (temperature drop)
CH Setting variation rate limiter (temperature drop) (in the Q compatible
mode)
■Setting range
• In the R mode
Set a value within the range of 0 to the full scale of the input range ( ()). When 0 is set, this setting is disabled.
• In the Q compatible mode
Set 0 or a value within the range of 1 to 1000 (0.1 to 100.0%) to the full scale of the input range set in 'CH1 Input range'
(Un\G501). When 0 is set, this setting is disabled.
■Default value
The default value is Disable (0).
CH1 Direct/reverse action setting
Select whether to use CH1 with direct actions or reverse actions.
Select direct actions for the cooling control. Select reverse actions for the heating control.
For details on the direct/reverse action selection function, refer to the following:
Page 54 Direct/reverse Action Selection Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Direct/reverse action setting
CH Direct/reverse action setting (in the Q compatible mode)
■Setting range
• 0: Direct action
• 1: Reverse action
■Default value
The default value is Reverse action (1).
APPX
272
Appendix 3 Buffer Memory Areas
CH1
CH2
514
714
564
596
CH1
CH2
515
715
54
86
CH3
CH4
914
1114
628
660
CH3
CH4
915
1115
118
150