Diagnostics Events; General - Bosch Praesideo Service Manual

Digital public address and emergency sound system
Table of Contents

Advertisement

Praesideo| Service manual | Chapter

9 Diagnostics Events

9.1

General

The diagnostic events are build up in the following way;
Date
YYYY-MM-DD
HH:MM:SS
The Fault events can be found in the configuration page under the "diagnose" tab.
There is also a NC logging tool available on the Software CD that logs the Fault events on your PC.
With this NC logging tool, Fault events can be saved and printed out.
Here below you will find the fault events with there description and advise on fault finding and solving.
Configuration Version
Description:
Fault finding:
Bosch Security Systems | 2004-28 | 3922 880 62312
Time
Activated By
Unit name & Serial Number
Logs the mismatch of the version number of the configuration file
and the version number of the software
Convert the configuration file to the proper version. See the release
note on the Software CD.
Delete the configuration file via the file transfer program and
reprogram the system
Status
Fault/reset/resolved
en | 22
Event
Fault description

Hide quick links:

Advertisement

Table of Contents
loading