Detailed instruction of parameters
1: Reserved
0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to
decrease the output frequency during the set time.
When the frequency decreases to P01.15, the
inverter stops.
1: Coast to stop: after the stop command becomes
valid, the inverter ceases the output immediately.
And the load coasts to stop at the mechanical
inertia.
The starting frequency of stop braking: the inverter
will carry on stop DC braking when the frequency is
arrived during the procedure of decelerating to
stop.
The waiting time of stop braking: before the stop
DC braking, the inverter will close output and begin
to carry on the DC braking after the waiting time.
This function is used to avoid the overcurrent fault
caused by DC braking when the speed is too high.
Stop DC braking current: the DC brake added. The
stronger the current, the bigger the DC braking
57
Function codes
Default
Modif
value
y
Reserv
◎
ed
Reserv
◎
ed
○
0
○
0.00Hz
○
0.00s
○
0.0%
○
0.0s