INVT Goodrive 300 Operation Manual page 200

Hide thumbs Also See for Goodrive 300:
Table of Contents

Advertisement

inverters
Goodrive300
Function
code
P06.05
P06.06
Y switch-on delay time
P06.07
Y switch-off delay time
P06.08
HDO switch-on delay time
P06.09
HDO switch-off delay time
P06.10
RO1 switch-on delay time 0.000~50.000s
Name
Polarity of output
terminals
Detailed instruction of parameters
6:Frequency degree test FDT1
7:Frequency degree test FDT2
8:Frequency arrival
9:Zero speed running
10:Upper limit frequency arrival
11:Lower limit frequency arrival
12:Ready for operation
13:Pre-magnetizing
14:Overload pre-alarm
15: Underload pre-alarm
16:Completion of simple PLC stage
17:Completion of simple PLC cycle
18:Setting count value arrival
19:Defined count value arrival
20:External fault valid
21:Length arrival
22:Running time arrival
23:MODBUS communication virtual
terminals output
24:PROFIBUS communication virtual
terminals output
25: Ethernet communication virtual
terminals output
26~30: Reserved
0x00~0x0F
0.000~50.000s
0.000~50.000s
0.000~50.000s
(valid only when P06.00=1)
0.000~50.000s
(valid only when P06.00=1)
199
Basic operation instruction
Default
value
0x00
0.000s
0.000s
0.000s
0.000s
0.000s