inverters
Goodrive300
Functi
on
Name
code
control
speed
Compensat
ion
P03.28
coefficient
of static
friction
Compensat
ion
P03.29
coefficient
of dyanmic
friction
P04 Group
V/F control
Motor 1V/F
P04.00
curve
setting
Detailed instruction of parameters
0.0~100.0%
Adjust P03.28 to compensate the coefficient of
static friction. Only valid when setting in 1Hz.
0.0~100.0%
Adjust P03.29 to compensate the coefficient of
static friction. Only valid when setting in 1Hz.
These function codes define the V/F curve of
Goodrive300 motor 1 to meet the need of different
loads.
0:Straight line V/F curve;applying to the constant
torque load
1:Multi-dots V/F curve
th
2:1.3
power low torque V/F curve
th
3:1.7
power low torque V/F curve
th
4:2.0
power low torque V/F curve
Curves 2~4 apply to the torque loads such as fans
and water pumps. Users can adjust according to
the features of the loads to achieve a best
energy-consuming effect.
5:Customized V/F(V/F separation); on this mode, V
and F can be separated from f and f can be
adjusted through the frequency given channel set
by P00.06 or the voltage given channel set by
73
Function codes
Default
Modif
value
y
0.0%
0.0%
◎
0
Need help?
Do you have a question about the Goodrive 300 and is the answer not in the manual?