HVAC Drive Programming Guide

3.12 Main Menu - LonWorks - Group 11

3.12.1 LonWorks, 11-**
Parameter group for all LonWorks specific parameters.
Parameters related to LonWorks ID.
11-00 Neuron ID
Range:
0 N/A*
[0 - 0 N/A]
11-10 Drive Profile
Option:
[0] *
VSD profile
[1]
Pump controller
11-15 LON Warning Word
Range:
0 N/A*
[0 - 65535 N/A]
Bit
Status
0
Internal fault
1
Internal fault
2
Internal fault
3
Internal fault
4
Internal fault
5
Invalid type change for nvoAnIn1
6
Invalid type change for nvoAnIn2
7
Invalid type change for nvo109AnIn1
8
Invalid type change for nvo109AnIn2
9
Invalid type change for nvo109AnIn3
10
Initialization error
11
Internal communication error
12
Software revision mismatch
13
Bus not active
14
Option not present
15
LON input (nvi/nci) exceeds limits
11-17 XIF Revision
Range:
0 N/A*
[0 - 0 N/A]
11-18 LonWorks Revision
Range:
0 N/A*
[0 - 0 N/A]
Function:
View the Neuron chip's unique Neuron ID number.
Function:
This parameter allows selecting between LONMARK Functional Profiles.
The Danfoss Profile and the Node Object are common for all profiles.
Function:
This parameter contains the LON specific warnings.
Function:
This parameter contains the version of the external interface file on the Neuron C chip on the LON
option.
Function:
This parameter contains the software version of the application program on the Neuron C chip on
the LON option.