Danfoss VLT HVAC Series Programming Manual page 117

Table of Contents

Advertisement

VLT
®
HVAC Drive Programming Guide
8-06 Reset Control Timeout
Option:
[0] *
Do not reset
[1]
Do reset
8-07 Diagnosis Trigger
Option:
[0] *
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
3.9.3 8-1* Ctrl. Word Settings
Parameters for configuring the option control word profile.
8-10 Control Profile
Option:
[0] *
FC profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
8-13 Configurable Status Word STW
Option:
[0]
No function
[1] *
Profile Default
[2]
Alarm 68 Only
[3]
Trip excl Alarm 68
[16]
T37 DI status
Function:
This parameter is active only when the choice
of-Timeout Function
.
Retains the set-up specified in par.8-04
control timeout.
Returns the adjustable frequency drive to the original set-up following a control word timeout. When
the value is set to
Do reset
[1], the adjustable frequency drive performs the reset and then imme-
diately reverts to the
Do not reset
Function:
This parameter has no function for LonWorks.
Function:
Select the interpretation of the control and status words corresponding to the installed serial com-
munication bus. Only the selections valid for the serial communication bus installed in slot A will be
visible in the LCP display.
Function:
This parameter enables configuration of bits 12 – 15 in the status word.
Function corresponds to the profile default selected in par.8-10
Only set in case of an Alarm 68.
Set in case of a trip, except if the trip is executed by an Alarm 68.
The bit indicates the status of terminal 37.
"0" indicates T37 is low (safe stop)
"1" indicates T37 is high (normal)
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Hold set-up
[0] has been selected in par.8-05
Control Timeout Function
, [Select set-up 1-4] following a
[0] setting.
Control Profile
End-