3 Parameter Description
[70]
SL Timeout 3
[71]
SL Timeout 4
[72]
SL Timeout 5
[73]
SL Timeout 6
[74]
SL Timeout 7
[80]
No Flow
[81]
Dry Pump
3
[82]
End of Curve
[83]
Broken Belt
13-52 SL Controller Action
Array [20]
Option:
[0] *
DISABLED
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10]
Select preset ref 0
[11]
Select preset ref 1
[12]
Select preset ref 2
[13]
Select preset ref 3
[14]
Select preset ref 4
[15]
Select preset ref 5
[16]
Select preset ref 6
[17]
Select preset ref 7
[18]
Select ramp 1
[19]
Select ramp 2
[22]
Run
[23]
Run reverse
[24]
Stop
[26]
Dcstop
[27]
Coast
3-132
Function:
Select the action corresponding to the SLC event. Actions are executed when the corresponding
event (defined in par.13-51
SL Controller Event
available for selection:
Changes the active set-up (par.0-10
Changes the active set-up (par.0-10
Changes the active set-up (par.0-10
Active Set-up
Changes the active set-up (par.0-10
other set-up commands coming from either the digital inputs or via a serial communication bus.
Selects preset reference 0.
Selects preset reference 1.
Selects preset reference 2.
Selects preset reference 3.
Selects preset reference 4.
Selects preset reference 5.
Selects preset reference 6.
Selects preset reference 7. If the active preset reference is changed, it will merge with other preset
reference commands coming from either the digital inputs or via a serial communication bus.
Selects ramp 1
Selects ramp 2
Issues a start command to the adjustable frequency drive.
Issues a start reverse command to the adjustable frequency drive.
Issues a stop command to the adjustable frequency drive.
The adjustable frequency drive coasts immediately. All stop commands including the coast com-
mand stop the SLC.
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Programming Guide
) is evaluated as true. The following actions are
Active Set-up
) to '1'.
Active Set-up
) to '2'.
Active Set-up
) to '3'.
) to '4'. If the set-up is changed, it will merge with

Advertisement

Table of Contents
loading

Table of Contents