3 Parameter Description
4-53 Warning Speed High
Range:
par.
4-13
[par. 4-52 - par. 4-13 RPM]
RPM*
3
NOTE!
Any changes in par.4-13
in par.4-13
If a different value is needed in par.4-53
[RPM]
!
4-54 Warning Reference Low
Range:
-999999.99
[-999999.999 - par. 4-55 N/A]
9 N/A*
4-55 Warning Reference High
Range:
999999.999
[par. 4-54 - 999999.999 N/A]
N/A*
4-56 Warning Feedback Low
Range:
-999999.99
[-999999.999 - par. 4-57 Proc-
9
Proc-
essCtrlUnit]
essCtrlU-
nit*
4-57 Warning Feedback High
Range:
999999.999
[par. 4-56 - 999999.999 ProcessCtr-
ProcessCtr-
lUnit]
lUnit*
4-58 Missing Motor Phase Function
Option:
[0]
Off
[1] *
On
3-44
Function:
Enter the n
HIGH
HIGH. The signal outputs can be programmed to produce a status signal on terminal 27 or 29, and
on relay output 01 or 02. Program the upper signal limit of the motor speed, n
working range of the adjustable frequency drive. Refer to the drawing in this section.
Motor Speed High Limit [RPM]
Motor Speed High Limit [RPM]
.
Warning Speed High
Function:
Enter the lower reference limit. When the actual reference falls below this limit, the display indicates
Ref Low. The signal outputs can be programmed to produce a status signal on terminal 27 or 29
and on relay output 01 or 02.
Function:
Enter the upper reference limit. When the actual reference exceeds this limit, the display reads Ref
High. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02.
Function:
Enter the lower feedback limit. When the feedback falls below this limit, the display reads Feedb
Low. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02.
Function:
Enter the upper feedback limit. When the feedback exceeds this limit, the display reads Feedb High.
The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02.
Function:
Displays an alarm in the event of a missing motor phase.
Select 100 ms to have a short detection time and alarm in the event of a missing motor phase. 100
ms is recommended for hoisting applications.
No alarm is displayed if a missing motor phase occurs.
An alarm is displayed if a missing motor phase occurs.
MG.11.C6.22 - VLT
value. When the motor speed exceeds this limit (n
Warning Speed High
will reset the value in par.4-53
, it must be set after programming of par.4-13
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Programming Guide
), the display reads SPEED
HIGH
, within the normal
HIGH
to the same value as set
Motor Speed High Limit