Danfoss VLT HVAC Series Programming Manual page 106

Table of Contents

Advertisement

3 Parameter Description
3.8.3 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
0.07 V*
[0.00 - par. 6-11 V]
3
6-11 Terminal 53 High Voltage
Range:
10.00 V*
[par. 6-10 - 10.00 V]
6-12 Terminal 53 Low Current
Range:
4.00 mA*
[0.00 - par. 6-13 mA]
6-13 Terminal 53 High Current
Range:
20.00 mA*
[par. 6-12 - 20.00 mA]
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
0.000 N/A*
[-999999.999 - 999999.999 N/A]
6-15 Terminal 53 High Ref./Feedb. Value
Range:
50.000
N/
[-999999.999 - 999999.999 N/A]
A*
6-16 Terminal 53 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
6-17 Terminal 53 Live Zero
Option:
[0]
Disabled
[1] *
Enabled
3-82
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
Terminal 53 Low Ref./Feedb. Value
feedback value set in par.6-14
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par.6-15
Function:
Enter the low current value. This reference signal should correspond to the low reference/feedback
Terminal 53 Low Ref./Feedb. Value
value, set in par.6-14
to activate the Live Zero Timeout Function in par.6-01
Function:
Enter the high current value corresponding to the high reference/feedback set in par.6-15
53 High Ref./Feedb. Value
.
Function:
Enter the analog input scaling value that corresponds to the low voltage/low current set in par.
6-10
Terminal 53 Low Voltage
and par.6-12
Function:
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
Terminal 53 High Voltage
par.6-11
and par.6-13
Function:
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 53. A high time constant value improves damping, but also increases the
time delay through the filter.
This parameter cannot be adjusted while the motor is running.
Function:
This parameter makes it possible to disable the Live Zero monitoring. For example, this is to be used
if the analog outputs are used as part of a de-central I/O system (e.g., when not used as part of
any adjustable frequency drive related control functions, but for feeding a building management
system with data).
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Programming Guide
.
Terminal 53 High Ref./Feedb. Value
.
. The value must be set at >2 mA in order
Live Zero Timeout Function
Terminal 53 Low Current
.
Terminal 53 High Current
.
Terminal
.