Danfoss VLT HVAC Series Programming Manual page 216

Table of Contents

Advertisement

3 Parameter Description
21-41 Ext. 2 Proportional Gain
Range:
0.01 N/A*
[0.00 - 10.00 N/A]
21-42 Ext. 2 Integral Time
Range:
10000.00
[0.01 - 10000.00 s]
3
s*
21-43 Ext. 2 Differentation Time
Range:
0.00 s*
[0.00 - 10.00 s]
21-44 Ext. 2 Dif. Gain Limit
Range:
5.0 N/A*
[1.0 - 50.0 N/A]
3.19.7 21-5* Closed-loop 3 Ref/Fb
Configure Extended Closed-loop 3 Controller reference and feedback.
21-50 Ext. 3 Ref./Feedback Unit
Option:
[0]
[1] *
%
[5]
PPM
[10]
min
[11]
RPM
[12]
PULSE/s
[20]
liter / sec.
[21]
liter / min
[22]
liter / hr.
[23]
m³ / sec.
[24]
m³/min
[25]
m³ / hr.
[30]
kg / sec.
[31]
kg/min
[32]
kg / hr.
[33]
ton / min
[34]
ton / hr.
[40]
m / sec.
[41]
m/min
[45]
m
[60]
°C
3-192
Function:
See par.21-21
Ext. 1 Proportional Gain
Function:
Ext. 1 Integral Time
See par.21-22
for details.
Function:
Ext. 1 Differentation Time
See par.21-23
Function:
Ext. 1 Dif. Gain Limit
See par.21-24
for details.
Function:
See par.21-10
Ext. 1 Ref./Feedback Unit
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Programming Guide
for details.
for details.
for details.