Danfoss VLT HVAC Series Programming Manual page 168

Table of Contents

Advertisement

3 Parameter Description
15-06 Reset kWh Counter
Option:
[0] *
Do not reset
[1]
Reset counter
NOTE!
3
The reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option:
[0] *
Do not reset
[1]
Reset counter
15-08 Number of Starts
Range:
0 N/A*
[0 - 2147483647 N/A]
NOTE!
This parameter will be reset when resetting par.15-07
3.15.3 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data sources (par.15-10
event (par.15-12
Trigger Event
15-10 Logging Source
Array [4]
Option:
[0] *
None
[1600]
Control Word
[1601]
Reference [Unit]
[1602]
Reference %
[1603]
Status Word
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor voltage
[1613]
Frequency
[1614]
Motor Current
[1616]
Torque [Nm]
3-144
Function:
Select
Do not reset
Select
Reset
[1] and press [OK] to reset the kWh counter to zero (see par.15-02
Function:
Do not reset
Select
Reset counter
Select
Hours
) and par.15-08
Function:
This is a readout parameter only. The counter shows the numbers of starts and stops caused by a
normal Start/Stop command and/or when entering/leaving sleep mode.
) and window (par.15-14
Samples Before Trigger
Function:
Select which variables are to be logged.
MG.11.C6.22 - VLT
VLT
[0] if no reset of the kWh counter is desired.
[0] if no reset of the Running Hours counter is desired.
[1] and press [OK] to reset the Running Hours counter (par.15-01
Number of Starts
to zero (see also par.15-01
Reset Running Hours Counter
.
Logging Source
) at individual rates (par.15-11
) are used to start and stop the logging conditionally.
®
is a registered Danfoss trademark
®
HVAC Drive Programming Guide
kWh Counter
).
Running
Running Hours
).
Logging Interval