Danfoss VLT HVAC Series Programming Manual page 119

Table of Contents

Advertisement

VLT
®
HVAC Drive Programming Guide
8-32 Baud Rate
Option:
[0]
2400 Baud
[1]
4800 Baud
[2] *
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option:
[0] *
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
10. ms*
[5. - 10000. ms]
8-36 Max Response Delay
Range:
10001. ms* [11. - 10001. ms]
8-37 Max Inter-Char Delay
Range:
25.00 ms*
[0.00 - 35.00 ms]
Function:
The baud rate selection depends on the protocol selection in par.8-30
Function:
Parity and Stop Bits for the protocol par.8-30
For some of the protocols, not all options will be visible. Default depends on the protocol selected.
Function:
Specify the minimum delay time between receiving a request and transmitting a response. This is
used for overcoming modem turnaround delays.
Function:
Specify the maximum permissible delay time between transmitting a request and receiving a re-
sponse. Exceeding this delay time will cause control word timeout.
Function:
Specify the maximum permissible time interval between receiving two bytes. This parameter acti-
vates timeout if transmission is interrupted.
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3 Parameter Description
Protocol
.
Protocol
using the Adjustable Frequency Drive Port.
3
3-95